Industrial Lubricated Rotary Vane Triplex Stack
The Global Vac & Air Triplex Lubricated Rotary Vane Industrial Stacked Vacuum System is built as two skids bolted together for ease of transport and installation. One skid consists of three lubricated rotary vane vacuum pumps mounted on a vertical frame stacked over one another and piped to a common manifold. The second skid consists of a mounted and wired triplex PLC control panel and vertical receiver. The system is completely tested before shipment and is built with a single point connection for process inlet, and system power. The complete assembly is finished in GLOBALVAC gray and supplied with inlet and discharge flex connectors and vibration pads. The system is piped, wired and factory tested prior to shipment.
Triplex PLC Control Panel
- Finger safe power distribution block
- 120V control transformer with CB protection for primary and secondary circuits
- 120vac/24vdc power supply
- 7” color OIT with integrated Hand/Off/Auto
- Door mounted system disconnect
- Door mounted Emergency Stop button
- Motor Circuit Protector/Disconnect for each pump externally operated
- Adjustable run-on timer (frequent start protection) integrated into OIT
- Automatic restart after power outage and restoration
- 4-20ma transmitter to control pumps via PLC input
- Selectable, Auto Timed Alternation (default), Auto Alternation or Manual Alternation
- Hourmeter integrated into OIT
- Pump status indicators integrated into OIT
- General system fault/warning integrated into OIT
- Dry contacts for remote monitoring
- Maintenance screens with adjustable time intervals for tracking critical maintenance items
- UL508A listed NEMA 12 enclosure
- Low vacuum alarm which may be enabled/disabled
- Door mounted Bypass circuit with selector switch, bypasses PLC control and allows continuous operation of all pumps using the motor circuit protector (MCP) disconnects as OFF/ON switches
- Panel mounted vacuum gauge
- StrideLinx cloud management (VPN)
- Ethernet bulkhead for temporary site connection
Model Number | Pump Motor Rating (HP) | Maximum Vacuum (” HgV) | Nominal Capacity (ACFM/pump) | System Capacity @ 19″ Hg (SCFM/system) | Receiver/Orientation | Spec Sheet |
---|---|---|---|---|---|---|
VR06T-XXD-20V | 6.4 | 29.9 | 116 | 127 | 200 | VRXXT-XXD-XXV |
VR08T-XXD-20V | 8.9 | 29.9 | 141 | 155 | 200 | |
VR12T-XXD-20V | 12.1 | 29.9 | 211 | 232 | 200 | |
VR12T-XXD-24V | 12.1 | 29.9 | 211 | 232 | 240 |